Heatshrinkable outdoor termination TTGEC3 W
Heatshrinkable outdoor termination TTGEC3 W
Heat-shrinkable MV outdoor terminations for paper insulated individually lead sheathed cables
Up to 19/33 (36) kV
Descrizione
Descrizione
Norme
-
TestHD 629.2 S2
Application
TTGEC3 w heat-shrinkable outdoor terminations are designed for mind individually lead sheathed cables with armour.
Technical description
The cables cores are prepared, the lead sheath is exposed and earthed.
The stress grading mastic covers the screen cut area onto the paper insulation. the lug is covered with silicone rubber tape.
Oil resistant tubing covers the cores.
Silicone rubber tape is used to block oil migration at the top and bottom of oil resistant tubing.
Stress control tubing is placed over oil barrier tube overlapping onto the lead sheath.
The crotch area and gaps are filled and covered with anti-tracking red mastic and is covered with a 3 finger anti-tracking breakout.
GT2 anti-tracking tubes protects the cores and additional gt2 tube is used for lug sealing.
Anti-tracking rain sheds are applied.
Armor and earth connection are included in the kit.