Description

Description

Standards

  • Product
    CEI 20-13; IEC 60502-1

Single core cables with aluminium conductor, elastomeric insulation, LSZH outer sheath.

Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.

Fire performance class:  Cca - s1b, d1, a1

Application:

Suitable for  environments with fire hazard where it is very important to ensure the safety of people and to preserve goods and equipments.

For fixed installation.

Construction:

  • Conductor:  solid, round aluminium – Cl. 1 (CEI EN 60228) (up to 10 mm2);
  • stranded, compacted, round aluminium – Cl. 2 (CEI EN 60228) (above 10 mm2).
  • Insulation: cross-linked compound. Colour: black.
  • Filler: extruded not hygroscopic compound.
  • Outer sheath: extruded LSZH compound. Colour: green. 

Functional characteristics:

  • Rated voltages U0/U: 0,6/1 kV
  • Max. operating temperature of conductor: 90°C
  • Max. short circuit temperature of conductor: 250°C (max 5s)
  • Min. installation temperature: 0°C
  • Max. tensile strength on the conductor during installation: 50 N/mm2
  • Min. bending radius during installation: 6 Dcable

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 IEC 60228
Insulation
Cross-linked compound
Insulation colour
Black
Lay Up
Material of filler / inner sheath
Not hygroscopic extruded compound
Outer sheath
Low smoke, zero halogen thermoplastic compound
Sheath colour
Green

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
400 mm²
Conductor diameter
23.5 mm
Average insulation thickness
2.0 mm
Diameter over insulation
27.8 mm
Average sheath thickness
2.0 mm
Nominal outer diameter
35.9 mm
Approximate weight
1690 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Max. DC resistance of the conductor at 20°C
0.0778 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.102 Ohm/km
Permissible short circuit current conductor 1s
37.8 kA

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000573-ITBP
  • Certification Date : 12/10/20
  • AVCP (Assessment and Verification of Constancy of Performance) : System 1+
  • Notified body : 0051
  • Declared performance : Cca-s1b,d1,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.