ARE4H5E 18/30kV SK1 (SHOCK PROOF 1)

Products

ARE4H5E 18/30kV 1x120 SK1

Nexans ref. 10540862

  • Conductor cross-section: 120 mm²
  • Conductor diameter: 13.1 mm
  • Minimum insulation thickness: 6.4 mm
  • Diameter over insulation: 27.7 mm
  • Nominal outer diameter: 40.6 mm
  • Approximate weight: 1340 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.325 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 252 A
  • Perm. current rating in air 30°C - trefoil formation: 332 A
  • Permissible short circuit current conductor 1s: 11.3 kA
  • Permissible short circuit current screen 0.5s: 2 kA

 

ARE4H5E 18/30kV 1x150 SK1

Nexans ref. 10513546

  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.3 mm
  • Minimum insulation thickness: 6.2 mm
  • Diameter over insulation: 28.5 mm
  • Nominal outer diameter: 41.5 mm
  • Approximate weight: 1430 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.265 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 281 A
  • Perm. current rating in air 30°C - trefoil formation: 375 A
  • Permissible short circuit current conductor 1s: 14.2 kA
  • Permissible short circuit current screen 0.5s: 2.1 kA

 

ARE4H5E 18/30kV 1x185 SK1

Nexans ref. 10540863

  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.0 mm
  • Minimum insulation thickness: 6.0 mm
  • Diameter over insulation: 29.8 mm
  • Nominal outer diameter: 42.8 mm
  • Approximate weight: 1560 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.211 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 318 A
  • Perm. current rating in air 30°C - trefoil formation: 430 A
  • Permissible short circuit current conductor 1s: 17.5 kA
  • Permissible short circuit current screen 0.5s: 2.1 kA

 

ARE4H5E 18/30kV 1x240 SK1

Nexans ref. 10506034

  • Conductor cross-section: 240 mm²
  • Conductor diameter: 18.5 mm
  • Minimum insulation thickness: 5.8 mm
  • Diameter over insulation: 31.9 mm
  • Nominal outer diameter: 45.0 mm
  • Approximate weight: 1790 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 369 A
  • Perm. current rating in air 30°C - trefoil formation: 508 A
  • Permissible short circuit current conductor 1s: 22.7 kA
  • Permissible short circuit current screen 0.5s: 2.2 kA

 

ARE4H5E 18/30kV 1x300 SK1

Nexans ref. 10506035

  • Conductor cross-section: 300 mm²
  • Conductor diameter: 20.7 mm
  • Minimum insulation thickness: 5.9 mm
  • Diameter over insulation: 34.3 mm
  • Nominal outer diameter: 47.6 mm
  • Approximate weight: 2040 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 416 A
  • Perm. current rating in air 30°C - trefoil formation: 583 A
  • Permissible short circuit current conductor 1s: 28.3 kA
  • Permissible short circuit current screen 0.5s: 2.3 kA

 

ARE4H5E 18/30kV 1x400 SK1

Nexans ref. 10540864

  • Conductor cross-section: 400 mm²
  • Conductor diameter: 23.5 mm
  • Minimum insulation thickness: 6.0 mm
  • Diameter over insulation: 37.3 mm
  • Nominal outer diameter: 50.7 mm
  • Approximate weight: 2380 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.101 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 476 A
  • Perm. current rating in air 30°C - trefoil formation: 680 A
  • Permissible short circuit current conductor 1s: 37.8 kA
  • Permissible short circuit current screen 0.5s: 2.5 kA

 

ARE4H5E 18/30kV 1x500 SK1

Nexans ref. 10506038

  • Conductor cross-section: 500 mm²
  • Conductor diameter: 26.5 mm
  • Minimum insulation thickness: 6.1 mm
  • Diameter over insulation: 40.8 mm
  • Nominal outer diameter: 54.4 mm
  • Approximate weight: 2820 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.079 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 543 A
  • Perm. current rating in air 30°C - trefoil formation: 790 A
  • Permissible short circuit current conductor 1s: 47.2 kA
  • Permissible short circuit current screen 0.5s: 2.7 kA

 

ARE4H5E 18/30kV 1x630 SK1

Nexans ref. 10509851

  • Conductor cross-section: 630 mm²
  • Conductor diameter: 30.0 mm
  • Minimum insulation thickness: 6.2 mm
  • Diameter over insulation: 44.5 mm
  • Nominal outer diameter: 58.3 mm
  • Approximate weight: 3360 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.063 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 617 A
  • Perm. current rating in air 30°C - trefoil formation: 918 A
  • Permissible short circuit current conductor 1s: 59.5 kA
  • Permissible short circuit current screen 0.5s: 2.9 kA

 

ARE4H5E 18/30kV 1x70 SK1

Nexans ref. 10531614

  • Conductor cross-section: 70 mm²
  • Conductor diameter: 9.8 mm
  • Minimum insulation thickness: 7.1 mm
  • Diameter over insulation: 25.8 mm
  • Nominal outer diameter: 38.6 mm
  • Approximate weight: 1150 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 186 A
  • Perm. current rating in air 30°C - trefoil formation: 238 A
  • Permissible short circuit current conductor 1s: 6.6 kA
  • Permissible short circuit current screen 0.5s: 1.9 kA

 

ARE4H5E 18/30kV 1x95 SK1

Nexans ref. 10513545

  • Conductor cross-section: 95 mm²
  • Conductor diameter: 11.5 mm
  • Minimum insulation thickness: 6.6 mm
  • Diameter over insulation: 26.5 mm
  • Nominal outer diameter: 39.4 mm
  • Approximate weight: 1230 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.411 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 222 A
  • Perm. current rating in air 30°C - trefoil formation: 288 A
  • Permissible short circuit current conductor 1s: 9 kA
  • Permissible short circuit current screen 0.5s: 1.9 kA

 

Description

Description

Standards

  • Product
    CEI 20-68; HD 620; IEC 60502-2

Description

Single core cables with aluminium conductor, reduced thickness XLPE insulation, aluminium tape screen, shock resistant PE outer sheath.

Application:

Suitable for fixed installation indoor or outdoor, laying in air or directly or indirectly buried. The special outer sheath provides an excellent protection against impacts and mechanical stress. Cables shock resistance has been evaluated by the abrasion and impact tests included in CEI 20-68 standard. This type of cable can be directly buried, without additional protections, because it is comparable to an armoured cable.

Construction

  • Conductor: stranded, compacted, round aluminium – Cl. 2 (IEC 60228).
  • Conductor screen: extruded semiconducting compound.
  • Insulation: extruded polyethylene (XLPE) compound.
  • Insulation screen: extruded semiconducting compound – fully bonded.
  • Longitudinal watertightness: semiconducting water blocking tape.
  • Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,2 mm).
  • Outer sheath: extruded polyethylene (PE) compound. Colour: red.

Functional characteristics

  • Rated voltages U0/U: 18/30 kV
  • Max. operating temperature of conductor: 90°C
  • Max. short circuit temperature of conductor: 250°C (max 5s)
  • Max. short circuit temperature of screen: 150°C
  • Min. installation temperature: -25°C
  • Max. tensile strength on the conductor during installation: 50 N/mm2
  • Min. bending radius during installation: 14 Dcable

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Material of the inner semi-conductor
Extruded semiconducting compound
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded semiconducting compound - fully bonded
Material used for longitudinal water tightness
Semiconducting swellable tape
Screen
Aluminium tape
Outer sheath
Extruded PE compound - impacts resistant
Sheath colour
Red

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Screen thickness
200 µm
Nominal outer sheath thickness
4.0 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
18 / 30 (36) kV
Thermal soil resistivity dry zone
1.5 °K.m/W
Grounding type
Solid bonding

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Shocks resistant, acc. to CEI 20-68

Usage characteristics

Usage characteristics

Laying depth, center of system
800 mm

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close