ARE4H5E 12/20kV 1x120 SR/0,2
Nexans ref. 10576454
- Conductor cross-section: 120 mm²
- Conductor diameter: 13.1 mm
- Minimum insulation thickness: 4.3 mm
- Diameter over insulation: 23.5 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 30.7 mm
- Approximate weight: 860 kg/km
- Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.325 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 252 A
- Perm. current rating in air 30°C - trefoil formation: 324 A
- Permissible short circuit current conductor 1s: 11.3 kA
- Permissible short circuit current screen 0.5s: 1.7 kA
ARE4H5E 12/20kV 1x150 SR/0,2
Nexans ref. 10576505
- Conductor cross-section: 150 mm²
- Conductor diameter: 14.3 mm
- Minimum insulation thickness: 4.3 mm
- Diameter over insulation: 24.7 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 31.9 mm
- Approximate weight: 960 kg/km
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.265 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 282 A
- Perm. current rating in air 30°C - trefoil formation: 367 A
- Permissible short circuit current conductor 1s: 14.2 kA
- Permissible short circuit current screen 0.5s: 1.8 kA
ARE4H5E 12/20kV 1x185 SR/0,2
Nexans ref. 10513560
- Conductor cross-section: 185 mm²
- Conductor diameter: 16.0 mm
- Minimum insulation thickness: 4.3 mm
- Diameter over insulation: 26.4 mm
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 33.8 mm
- Approximate weight: 1100 kg/km
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.211 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 319 A
- Perm. current rating in air 30°C - trefoil formation: 422 A
- Permissible short circuit current conductor 1s: 17.5 kA
- Permissible short circuit current screen 0.5s: 1.8 kA
ARE4H5E 12/20kV 1x240 SR/0,2
Nexans ref. 10530958
- Conductor cross-section: 240 mm²
- Conductor diameter: 18.5 mm
- Minimum insulation thickness: 4.3 mm
- Diameter over insulation: 28.9 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 36.6 mm
- Approximate weight: 1330 kg/km
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 370 A
- Perm. current rating in air 30°C - trefoil formation: 502 A
- Permissible short circuit current conductor 1s: 22.7 kA
- Permissible short circuit current screen 0.5s: 2 kA
ARE4H5E 12/20kV 1x300 SR/0,2
Nexans ref. 10505662
- Conductor cross-section: 300 mm²
- Conductor diameter: 20.7 mm
- Minimum insulation thickness: 4.4 mm
- Diameter over insulation: 31.3 mm
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 39.4 mm
- Approximate weight: 1560 kg/km
- Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 417 A
- Perm. current rating in air 30°C - trefoil formation: 578 A
- Permissible short circuit current conductor 1s: 28.3 kA
- Permissible short circuit current screen 0.5s: 2.1 kA
ARE4H5E 12/20kV 1x400 SR/0,2
Nexans ref. 10513359
- Conductor cross-section: 400 mm²
- Conductor diameter: 23.5 mm
- Minimum insulation thickness: 4.4 mm
- Diameter over insulation: 34.1 mm
- Nominal outer sheath thickness: 2.3 mm
- Nominal outer diameter: 42.4 mm
- Approximate weight: 1860 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.101 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 477 A
- Perm. current rating in air 30°C - trefoil formation: 676 A
- Permissible short circuit current conductor 1s: 37.8 kA
- Permissible short circuit current screen 0.5s: 2.3 kA
ARE4H5E 12/20kV 1x500 SR/0,2
Nexans ref. 10513370
- Conductor cross-section: 500 mm²
- Conductor diameter: 26.5 mm
- Minimum insulation thickness: 4.5 mm
- Diameter over insulation: 37.6 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 46.3 mm
- Approximate weight: 2280 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.08 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 544 A
- Perm. current rating in air 30°C - trefoil formation: 788 A
- Permissible short circuit current conductor 1s: 47.2 kA
- Permissible short circuit current screen 0.5s: 2.5 kA
ARE4H5E 12/20kV 1x630 SR/0,2
Nexans ref. 10549909
- Conductor cross-section: 630 mm²
- Conductor diameter: 30.0 mm
- Minimum insulation thickness: 4.6 mm
- Diameter over insulation: 41.3 mm
- Nominal outer sheath thickness: 2.5 mm
- Nominal outer diameter: 50.3 mm
- Approximate weight: 2790 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.063 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 618 A
- Perm. current rating in air 30°C - trefoil formation: 918 A
- Permissible short circuit current conductor 1s: 59.5 kA
- Permissible short circuit current screen 0.5s: 2.7 kA
ARE4H5E 12/20kV 1x70 SR/0,2
Nexans ref. 10505659
- Conductor cross-section: 70 mm²
- Conductor diameter: 9.8 mm
- Minimum insulation thickness: 4.7 mm
- Diameter over insulation: 21.0 mm
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 27.8 mm
- Approximate weight: 670 kg/km
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 186 A
- Perm. current rating in air 30°C - trefoil formation: 230 A
- Permissible short circuit current conductor 1s: 6.6 kA
- Permissible short circuit current screen 0.5s: 1.6 kA
ARE4H5E 12/20kV 1x95 SR/0,2
Nexans ref. 10513561
- Conductor cross-section: 95 mm²
- Conductor diameter: 11.5 mm
- Minimum insulation thickness: 4.5 mm
- Diameter over insulation: 22.3 mm
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 29.4 mm
- Approximate weight: 770 kg/km
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.411 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 222 A
- Perm. current rating in air 30°C - trefoil formation: 280 A
- Permissible short circuit current conductor 1s: 9 kA
- Permissible short circuit current screen 0.5s: 1.6 kA
Description
Description
Standards
-
ProductHD 620; IEC 60502-2
Description
Single core cables with aluminium conductor, reduced thickness XLPE insulation, aluminium tape screen, PE outer sheath.
Application:
Suitable for fixed installation indoor or outdoor, laying in air or directly or indirectly buried.
Construction
- Conductor: stranded, compacted, round aluminium – Cl. 2 (IEC 60228).
- Conductor screen: extruded semiconducting compound.
- Insulation: extruded polyethylene (XLPE) compound.
- Insulation screen: extruded semiconducting compound – fully bonded.
- Longitudinal watertightness: semiconducting water blocking tape.
- Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,2 mm).
- Outer sheath: extruded polyethylene (PE) compound. Colour: red.
Functional characteristics
- Rated voltages U0/U: 12/20 kV
- Max. operating temperature of conductor: 90°C
- Max. short circuit temperature of conductor: 250°C (max 5s)
- Max. short circuit temperature of screen: 150°C
- Min. installation temperature: -25°C
- Max. tensile strength on the conductor during installation: 50 N/mm2
- Min. bending radius during installation: 14 Dcable
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Material of the inner semi-conductor
Extruded semiconducting compound
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded semiconducting compound - fully bonded
Material used for longitudinal water tightness
Semiconducting swellable tape
Screen
Aluminium tape
Outer sheath
Extruded PE compound
Sheath colour
Red
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Screen thickness
200 µm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Thermal soil resistivity dry zone
1.5 °K.m/W
Grounding type
Solid bonding
Usage characteristics
Usage characteristics
Laying depth, center of system
800 mm
Resources