ARE4H5E 18/30kV 1x120 SR/0,2
Nexans ref. 10544047
- Conductor cross-section: 120 mm²
- Conductor diameter: 13.1 mm
- Minimum insulation thickness: 6.4 mm
- Diameter over insulation: 27.7 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 35.4 mm
- Approximate weight: 1070 kg/km
- Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.325 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 253 A
- Perm. current rating in air 30°C - trefoil formation: 329 A
- Permissible short circuit current conductor 1s: 11.3 kA
- Permissible short circuit current screen 0.5s: 2 kA
ARE4H5E 18/30kV 1x150 SR/0,2
Nexans ref. 10567887
- Conductor cross-section: 150 mm²
- Conductor diameter: 14.3 mm
- Minimum insulation thickness: 6.2 mm
- Diameter over insulation: 28.5 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 36.2 mm
- Approximate weight: 1160 kg/km
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.265 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 282 A
- Perm. current rating in air 30°C - trefoil formation: 371 A
- Permissible short circuit current conductor 1s: 14.2 kA
- Permissible short circuit current screen 0.5s: 2.1 kA
ARE4H5E 18/30kV 1x185 SR/0,2
Nexans ref. 10512204
- Conductor cross-section: 185 mm²
- Conductor diameter: 16.0 mm
- Minimum insulation thickness: 6.0 mm
- Diameter over insulation: 29.8 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 37.6 mm
- Approximate weight: 1280 kg/km
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.211 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 319 A
- Perm. current rating in air 30°C - trefoil formation: 426 A
- Permissible short circuit current conductor 1s: 17.5 kA
- Permissible short circuit current screen 0.5s: 2.1 kA
ARE4H5E 18/30kV 1x240 SR/0,2
Nexans ref. 10506027
- Conductor cross-section: 240 mm²
- Conductor diameter: 18.5 mm
- Minimum insulation thickness: 5.8 mm
- Diameter over insulation: 31.9 mm
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 40.0 mm
- Approximate weight: 1510 kg/km
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 370 A
- Perm. current rating in air 30°C - trefoil formation: 505 A
- Permissible short circuit current conductor 1s: 22.7 kA
- Permissible short circuit current screen 0.5s: 2.2 kA
ARE4H5E 18/30kV 1x300 SR/0,2
Nexans ref. 10547468
- Conductor cross-section: 300 mm²
- Conductor diameter: 20.7 mm
- Minimum insulation thickness: 5.9 mm
- Diameter over insulation: 34.3 mm
- Nominal outer sheath thickness: 2.3 mm
- Nominal outer diameter: 42.6 mm
- Approximate weight: 1740 kg/km
- Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 418 A
- Perm. current rating in air 30°C - trefoil formation: 580 A
- Permissible short circuit current conductor 1s: 28.3 kA
- Permissible short circuit current screen 0.5s: 2.3 kA
ARE4H5E 18/30kV 1x400 SR/0,2
Nexans ref. 10544048
- Conductor cross-section: 400 mm²
- Conductor diameter: 23.5 mm
- Minimum insulation thickness: 6.0 mm
- Diameter over insulation: 37.3 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 46.0 mm
- Approximate weight: 2070 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.101 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 477 A
- Perm. current rating in air 30°C - trefoil formation: 678 A
- Permissible short circuit current conductor 1s: 37.8 kA
- Permissible short circuit current screen 0.5s: 2.5 kA
ARE4H5E 18/30kV 1x500 SR/0,2
Nexans ref. 10515583
- Conductor cross-section: 500 mm²
- Conductor diameter: 26.5 mm
- Minimum insulation thickness: 6.1 mm
- Diameter over insulation: 40.8 mm
- Nominal outer sheath thickness: 2.5 mm
- Nominal outer diameter: 49.8 mm
- Approximate weight: 2500 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.08 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 545 A
- Perm. current rating in air 30°C - trefoil formation: 790 A
- Permissible short circuit current conductor 1s: 47.2 kA
- Permissible short circuit current screen 0.5s: 2.7 kA
ARE4H5E 18/30kV 1x630 SR/0,2
Nexans ref. 10512205
- Conductor cross-section: 630 mm²
- Conductor diameter: 30.0 mm
- Minimum insulation thickness: 6.2 mm
- Diameter over insulation: 44.5 mm
- Nominal outer sheath thickness: 2.6 mm
- Nominal outer diameter: 53.9 mm
- Approximate weight: 3030 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.063 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 620 A
- Perm. current rating in air 30°C - trefoil formation: 920 A
- Permissible short circuit current conductor 1s: 59.5 kA
- Permissible short circuit current screen 0.5s: 2.9 kA
ARE4H5E 18/30kV 1x70 SR/0,2
Nexans ref. 10514335
- Conductor cross-section: 70 mm²
- Conductor diameter: 9.8 mm
- Minimum insulation thickness: 7.1 mm
- Diameter over insulation: 25.8 mm
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 33.2 mm
- Approximate weight: 880 kg/km
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 187 A
- Perm. current rating in air 30°C - trefoil formation: 235 A
- Permissible short circuit current conductor 1s: 6.6 kA
- Permissible short circuit current screen 0.5s: 1.9 kA
ARE4H5E 18/30kV 1x95 SR/0,2
Nexans ref. 10512203
- Conductor cross-section: 95 mm²
- Conductor diameter: 11.5 mm
- Minimum insulation thickness: 6.6 mm
- Diameter over insulation: 26.5 mm
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 33.9 mm
- Approximate weight: 960 kg/km
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.411 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 222 A
- Perm. current rating in air 30°C - trefoil formation: 284 A
- Permissible short circuit current conductor 1s: 9 kA
- Permissible short circuit current screen 0.5s: 1.9 kA
Description
Description
Standards
-
ProductHD 620; IEC 60502-2
Description
Single core cables with aluminium conductor, reduced thickness XLPE insulation, aluminium tape screen, PE outer sheath.
Application:
Suitable for fixed installation indoor or outdoor, laying in air or directly or indirectly buried.
Construction
- Conductor: stranded, compacted, round aluminium – Cl. 2 (IEC 60228).
- Conductor screen: extruded semiconducting compound.
- Insulation: extruded polyethylene (XLPE) compound.
- Insulation screen: extruded semiconducting compound – fully bonded.
- Longitudinal watertightness: semiconducting water blocking tape.
- Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,2 mm).
- Outer sheath: extruded polyethylene (PE) compound. Colour: red.
Functional characteristics
- Rated voltages U0/U: 18/30 kV
- Max. operating temperature of conductor: 90°C
- Max. short circuit temperature of conductor: 250°C (max 5s)
- Max. short circuit temperature of screen: 150°C
- Min. installation temperature: -25°C
- Max. tensile strength on the conductor during installation: 50 N/mm2
- Min. bending radius during installation: 14 Dcable
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Material of the inner semi-conductor
Extruded semiconducting compound
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded semiconducting compound - fully bonded
Material used for longitudinal water tightness
Semiconducting swellable tape
Screen
Aluminium tape
Outer sheath
Extruded PE compound
Sheath colour
Red
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Screen thickness
200 µm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
18 / 30 (36) kV
Thermal soil resistivity dry zone
1.5 °K.m/W
Grounding type
Solid bonding
Usage characteristics
Usage characteristics
Laying depth, center of system
800 mm
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania