ARE4H5EE 12/20kV SK2 (SHOCK PROOF 2)

Products

ARE4H5EE 12/20kV 1x150 SK2

Nexans ref. 10558566

  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.3 mm
  • Minimum insulation thickness: 4.3 mm
  • Diameter over insulation: 24.7 mm
  • Nominal outer diameter: 37.5 mm
  • Approximate weight: 1220 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.265 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 280 A
  • Perm. current rating in air 30°C - trefoil formation: 372 A
  • Permissible short circuit current conductor 1s: 14.2 kA
  • Permissible short circuit current screen 0.5s: 1.8 kA

 

ARE4H5EE 12/20kV 1x185 SK2

Nexans ref. 10571798

  • Conductor cross-section: 185 mm²
  • Conductor diameter: 16.0 mm
  • Minimum insulation thickness: 4.3 mm
  • Diameter over insulation: 26.4 mm
  • Nominal outer diameter: 39.3 mm
  • Approximate weight: 1370 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.211 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 317 A
  • Perm. current rating in air 30°C - trefoil formation: 428 A
  • Permissible short circuit current conductor 1s: 17.5 kA
  • Permissible short circuit current screen 0.5s: 1.8 kA

 

ARE4H5EE 12/20kV 1x240 SK2

Nexans ref. 10538054

  • Conductor cross-section: 240 mm²
  • Conductor diameter: 18.5 mm
  • Minimum insulation thickness: 4.3 mm
  • Diameter over insulation: 28.9 mm
  • Nominal outer diameter: 41.9 mm
  • Approximate weight: 1610 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 368 A
  • Perm. current rating in air 30°C - trefoil formation: 507 A
  • Permissible short circuit current conductor 1s: 22.7 kA
  • Permissible short circuit current screen 0.5s: 2 kA

 

ARE4H5EE 12/20kV 1x630 SK2

Nexans ref. 10571812

  • Conductor cross-section: 630 mm²
  • Conductor diameter: 30.0 mm
  • Minimum insulation thickness: 4.6 mm
  • Diameter over insulation: 41.3 mm
  • Nominal outer diameter: 54.9 mm
  • Approximate weight: 3110 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.063 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 616 A
  • Perm. current rating in air 30°C - trefoil formation: 918 A
  • Permissible short circuit current conductor 1s: 59.5 kA
  • Permissible short circuit current screen 0.5s: 2.7 kA

 

ARE4H5EE 12/20kV 1x70 SK2

Nexans ref. 10558565

  • Conductor cross-section: 70 mm²
  • Conductor diameter: 9.8 mm
  • Minimum insulation thickness: 4.7 mm
  • Diameter over insulation: 21.0 mm
  • Nominal outer diameter: 33.6 mm
  • Approximate weight: 900 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 185 A
  • Perm. current rating in air 30°C - trefoil formation: 235 A
  • Permissible short circuit current conductor 1s: 6.6 kA
  • Permissible short circuit current screen 0.5s: 1.6 kA

 

Description

Description

Standards

  • Product
    CEI 20-68; HD 620; IEC 60502-2

Description

Single core cables with aluminium conductor, reduced thickness XLPE insulation, aluminium tape screen, double shock resistant PE sheath.

Application:

Suitable for fixed installation indoor or outdoor, laying in air or directly or indirectly buried. The two special sheaths provide an excellent protection against impacts and mechanical stress. Cables shock resistance has been evaluated by the abrasion and impact tests included in CEI 20-68 standard. This type of cable can be directly buried, without additional protections, because it is comparable to an armoured cable.

Construction

  • Conductor: stranded, compacted, round aluminium – Cl. 2 (IEC 60228).
  • Conductor screen: extruded semiconducting compound.
  • Insulation: extruded polyethylene (XLPE) compound.
  • Insulation screen: extruded semiconducting compound – fully bonded.
  • Longitudinal watertightness: semiconducting water blocking tape.
  • Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,2 mm).
  • First sheath: extruded polyethylene (PE) compound.
  • Second sheath: extruded polyethylene (PE) compound. Colour: red.

Functional characteristics

  • Rated voltages U0/U: 12/20 kV
  • Max. operating temperature of conductor: 90°C
  • Max. short circuit temperature of conductor: 250°C (max 5s)
  • Max. short circuit temperature of screen: 150°C
  • Min. installation temperature: -25°C
  • Max. tensile strength on the conductor during installation: 50 N/mm2
  • Min. bending radius during installation: 14 Dcable

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Material of the inner semi-conductor
Extruded semiconducting compound
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded semiconducting compound - fully bonded
Material used for longitudinal water tightness
Semiconducting swellable tape
Screen
Aluminium tape
Inner sheath
Extruded PE compound - impacts resistant
Outer sheath
Extruded PE compound - impacts resistant
Sheath colour
Red

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Screen thickness
200 µm
Inner sheath thickness
2.0 mm
Nominal outer sheath thickness
2.0 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Thermal soil resistivity dry zone
1.5 °K.m/W
Grounding type
Solid bonding

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Shocks resistant, acc. to CEI 20-68

Usage characteristics

Usage characteristics

Laying depth, center of system
800 mm

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close