- Markets
- Products
- Newsroom
- About Nexans
- Tools & Resources
- Search
- Contact us
- Compare
- Sign in
ARE4H5EEX 18/30kV 3x1x150 SK2
Nexans ref. 10581121
- Phase Conductor Cross Section: 150 mm²
- Phase Conductor Diameter: 14.3 mm
- Minimum insulation thickness: 6.2 mm
- Diameter over insulation: 28.5 mm
- Nominal overall diameter of each phase cable: 41.5 mm
- Nominal overall diameter: 89.4 mm
- Approximate weight: 4300 kg/km
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.265 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 281 A
- Perm. current rating in air 30°C - trefoil formation: 375 A
- Permissible short circuit current conductor 1s: 14.2 kA
- Permissible short circuit current screen 0.5s: 2.1 kA
ARE4H5EEX 18/30kV 3x1x185 SK2
Nexans ref. 10564808
- Phase Conductor Cross Section: 185 mm²
- Phase Conductor Diameter: 16 mm
- Minimum insulation thickness: 6.0 mm
- Diameter over insulation: 29.8 mm
- Nominal overall diameter of each phase cable: 42.8 mm
- Nominal overall diameter: 92.3 mm
- Approximate weight: 4700 kg/km
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.211 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 318 A
- Perm. current rating in air 30°C - trefoil formation: 430 A
- Permissible short circuit current conductor 1s: 17.5 kA
- Permissible short circuit current screen 0.5s: 2.1 kA
ARE4H5EEX 18/30kV 3x1x240 SK2
Nexans ref. 10568664
- Phase Conductor Cross Section: 240 mm²
- Phase Conductor Diameter: 18.5 mm
- Minimum insulation thickness: 5.8 mm
- Diameter over insulation: 31.9 mm
- Nominal overall diameter of each phase cable: 45 mm
- Nominal overall diameter: 97.0 mm
- Approximate weight: 5380 kg/km
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 369 A
- Perm. current rating in air 30°C - trefoil formation: 508 A
- Permissible short circuit current conductor 1s: 22.7 kA
- Permissible short circuit current screen 0.5s: 2.2 kA
ARE4H5EEX 18/30kV 3x1x300 SK2
Nexans ref. 10548531
- Phase Conductor Cross Section: 300 mm²
- Phase Conductor Diameter: 20.7 mm
- Minimum insulation thickness: 5.9 mm
- Diameter over insulation: 34.3 mm
- Nominal overall diameter of each phase cable: 47.6 mm
- Nominal overall diameter: 102.5 mm
- Approximate weight: 6120 kg/km
- Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.129 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 416 A
- Perm. current rating in air 30°C - trefoil formation: 583 A
- Permissible short circuit current conductor 1s: 28.3 kA
- Permissible short circuit current screen 0.5s: 2.3 kA
ARE4H5EEX 18/30kV 3x1x400 SK2
Nexans ref. 10568665
- Phase Conductor Cross Section: 400 mm²
- Phase Conductor Diameter: 23.5 mm
- Minimum insulation thickness: 6.0 mm
- Diameter over insulation: 37.3 mm
- Nominal overall diameter of each phase cable: 50.7 mm
- Nominal overall diameter: 109.3 mm
- Approximate weight: 7140 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.101 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 476 A
- Perm. current rating in air 30°C - trefoil formation: 680 A
- Permissible short circuit current conductor 1s: 37.8 kA
- Permissible short circuit current screen 0.5s: 2.5 kA
ARE4H5EEX 18/30kV 3x1x70 SK2
Nexans ref. 10548530
- Phase Conductor Cross Section: 70 mm²
- Phase Conductor Diameter: 9.8 mm
- Minimum insulation thickness: 7.1 mm
- Diameter over insulation: 25.8 mm
- Nominal overall diameter of each phase cable: 38.6 mm
- Nominal overall diameter: 83.3 mm
- Approximate weight: 3440 kg/km
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.568 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 186 A
- Perm. current rating in air 30°C - trefoil formation: 238 A
- Permissible short circuit current conductor 1s: 6.6 kA
- Permissible short circuit current screen 0.5s: 1.9 kA
ARE4H5EEX 18/30kV 3x1x95 SK2
Nexans ref. 10544979
- Phase Conductor Cross Section: 95 mm²
- Phase Conductor Diameter: 11.5 mm
- Minimum insulation thickness: 6.6 mm
- Diameter over insulation: 26.5 mm
- Nominal overall diameter of each phase cable: 39.4 mm
- Nominal overall diameter: 84.8 mm
- Approximate weight: 3680 kg/km
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.411 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 222 A
- Perm. current rating in air 30°C - trefoil formation: 288 A
- Permissible short circuit current conductor 1s: 9 kA
- Permissible short circuit current screen 0.5s: 1.9 kA
Description
Description
Standards
-
ProductCEI 20-68; HD 620; IEC 60502-2
Description
Helically bundled tripolar cables with aluminium conductor, reduced thickness XLPE insulation, aluminium tape screen, double shock resistant PE sheath.
Application:
Suitable for fixed installation indoor or outdoor, laying in air or directly or indirectly buried. The two special sheaths provide an excellent protection against impacts and mechanical stress. Cables shock resistance has been evaluated by the abrasion and impact tests included in CEI 20-68 standard. This type of cable can be directly buried, without additional protections, because it is comparable to an armoured cable.
Construction
- Conductor: stranded, compacted, round aluminium – Cl. 2 (IEC 60228).
- Conductor screen: extruded semiconducting compound.
- Insulation: extruded polyethylene (XLPE) compound.
- Insulation screen: extruded semiconducting compound – fully bonded.
- Longitudinal watertightness: semiconducting water blocking tape.
- Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,2 mm).
- First sheath: extruded polyethylene (PE) compound.
- Second sheath: extruded polyethylene (PE) compound. Colour: red.
Functional characteristics
- Rated voltages U0/U: 18/30 kV
- Max. operating temperature of conductor: 90°C
- Max. short circuit temperature of conductor: 250°C (max 5s)
- Max. short circuit temperature of screen: 150°C
- Min. installation temperature: -25°C
- Max. tensile strength on the conductor during installation: 50 N/mm2
- Min. bending radius during installation: 21 Dphase
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania