ARE4H5EX 12/20kV 3x1x185
ARE4H5EX 12/20kV 3x1x185
- Nexans ref. : 10566040
Description
Description
Standards
-
ProductCEI 20-68; IEC 60502-2
Helically bundled tripolar cables with aluminium conductor, XLPE insulation, aluminium tape screen, PE outer sheath.
Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.
Fire performance class: Fca
Application:
Suitable for fixed installation laying in air or indirectly buried.
Construction:
- Conductor: stranded, compacted, round aluminium – Cl. 2 (IEC 60228).
- Conductor screen: extruded semiconducting compound.
- Insulation: extruded polyethylene (XLPE) compound.
- Insulation screen: extruded semiconducting compound – fully bonded.
- Longitudinal watertightness: semiconducting water blocking tape.
- Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,3 mm).
- Outer sheath: extruded polyethylene (PE) compound. Colour: red.
Functional characteristics:
- Rated voltages U0/U: 12/20 kV
- Max. operating temperature of conductor: 90°C
- Max. short circuit temperature of conductor: 250°C (max 5s)
- Max. short circuit temperature of screen: 150°C
- Min. installation temperature: -25°C
- Max. tensile strength on the conductor during installation: 50 N/mm2
- Min. bending radius during installation: 21 Dphase
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Material of the inner semi-conductor
Extruded semiconducting compound
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded semiconducting compound - fully bonded
Material used for longitudinal water tightness
Semiconducting swellable tape
Screen
Aluminium tape
Outer sheath
Extruded PE compound
Sheath colour
Red
Lay Up
Twisted single cores
Dimensional characteristics
Dimensional characteristics
Number of phases
3
Phase Conductor Cross Section
185 mm²
Phase Conductor Diameter
16 mm
Minimum insulation thickness
4.3 mm
Diameter over insulation
26.4 mm
Screen thickness
300 µm
Nominal outer sheath thickness
2.0 mm
Nominal overall diameter of each phase cable
34 mm
Nominal overall diameter
73.3 mm
Approximate weight
3390 kg/km
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Max. DC resistance of the conductor at 20°C
0.164 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.211 Ohm/km
Perm. current rating buried 20°C - trefoil formation
360 A
Permissible short circuit current conductor 0.5s
24 kA
Permissible short circuit current screen 0.5s
2.8 kA
Thermal soil resistivity dry zone
1 °K.m/W
Grounding type
Solid bonding
Usage characteristics
Usage characteristics
Laying depth, center of system
1200 mm
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1000957-ITBP
- Certification Date : 12/10/20
- AVCP (Assessment and Verification of Constancy of Performance) : System 4
- Declared performance : Fca