ARP1H5EX 12/20kV 3x1x185

Description

Description

Standards

  • Product
    CEI 20-86; HD 620

Helically bundled tripolar cables with aluminium conductor, HPTE insulation, aluminium tape screen, PE outer sheath.

Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.

Fire performance class:  Eca

Application:

Suitable for fixed installation laying indirectly buried.

Construction:

  • Conductor: stranded, compacted, round aluminium – Cl. 2 (IEC 60228).
  • Conductor screen: extruded semiconducting compound.
  • Insulation: extruded high performance polypropylene thermoplastic elastomer (HPTE) compound.
  • Insulation screen: extruded semiconducting compound – easy strippable.
  • Longitudinal watertightness: semiconducting water blocking tape.
  • Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,3 mm).
  • Outer sheath: extruded polyethylene (PE) compound. Colour: red.

Functional characteristics:

  • Rated voltages U0/U: 12/20 kV
  • Max. operating temperature of conductor: 90°C
  • Max. short circuit temperature of conductor: 250°C (max 5s)
  • Max. short circuit temperature of screen: 150°C
  • Min. installation temperature: -25°C
  • Max. tensile strength on the conductor during installation: 50 N/mm2
  • Min. bending radius during installation: 21 Dphase

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Material of the inner semi-conductor
Extruded semiconducting compound
Insulation
Extruded HPTE compound
Material of the external semi-conductor
Extruded semiconducting compound - easy strippable
Material used for longitudinal water tightness
Semiconducting swellable tape
Screen
Aluminium tape
Outer sheath
Extruded PE compound
Sheath colour
Red
Lay Up
Twisted single cores

Dimensional characteristics

Dimensional characteristics

Number of phases
3
Phase Conductor Cross Section
185 mm²
Phase Conductor Diameter
16 mm
Nominal insulation thickness
4.9 mm
Minimum insulation thickness
4.31 mm
Diameter over insulation
26.4 mm
Screen thickness
300 µm
Nominal outer sheath thickness
2.75 mm
Nominal overall diameter of each phase cable
35.5 mm
Nominal overall diameter
76.4 mm
Approximate weight
3690 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Max. DC resistance of the conductor at 20°C
0.164 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.211 Ohm/km
Perm. current rating buried 20°C - trefoil formation
314 A
Permissible short circuit current conductor 1s
17.5 kA
Permissible short circuit current screen 0.5s
2.8 kA
Thermal soil resistivity dry zone
1.5 °K.m/W
Grounding type
Solid bonding

Usage characteristics

Usage characteristics

Laying depth, center of system
800 mm

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000921-ITBP
  • Certification Date : 12/10/20
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0051
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error