ARE4E(X) 0,6/1kV / Eca
ARE4E 0,6/1kV 1x150 IT
Nexans ref. 10548246
- With smaller neutral conductor: No
- Neutral Type:
- Lay Up: Single core
- Number of cores: 1
- Number of phases: -
- Conductor cross-section: 150 mm²
- Phase Conductor Cross Section: - mm²
- Neutral conductor section (when smaller): - mm²
- Conductor diameter: 14.3 mm
- Phase Conductor Diameter: - mm
- Neutral Conductor Diameter: - mm
- Average insulation thickness: 1.4 mm
- Insulation thickness of neutral conductor: - mm
- Average sheath thickness: 1.4 mm
- Nominal outer diameter: 21.6 mm
- Nominal overall diameter of each phase cable: - mm
- Nominal overall diameter: - mm
- Approximate weight: 560 kg/km
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- Permissible short circuit current conductor 1s: 14.1 kA
ARE4E 0,6/1kV 1x240 IT
Nexans ref. 10548247
- With smaller neutral conductor: No
- Neutral Type:
- Lay Up: Single core
- Number of cores: 1
- Number of phases: -
- Conductor cross-section: 240 mm²
- Phase Conductor Cross Section: - mm²
- Neutral conductor section (when smaller): - mm²
- Conductor diameter: 18.5 mm
- Phase Conductor Diameter: - mm
- Neutral Conductor Diameter: - mm
- Average insulation thickness: 1.7 mm
- Insulation thickness of neutral conductor: - mm
- Average sheath thickness: 1.5 mm
- Nominal outer diameter: 26.9 mm
- Nominal overall diameter of each phase cable: - mm
- Nominal overall diameter: - mm
- Approximate weight: 880 kg/km
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- Permissible short circuit current conductor 1s: 22.7 kA
ARE4E 0,6/1kV 1x25 IT
Nexans ref. 10548228
- With smaller neutral conductor: No
- Neutral Type:
- Lay Up: Single core
- Number of cores: 1
- Number of phases: -
- Conductor cross-section: 25 mm²
- Phase Conductor Cross Section: - mm²
- Neutral conductor section (when smaller): - mm²
- Conductor diameter: 6.0 mm
- Phase Conductor Diameter: - mm
- Neutral Conductor Diameter: - mm
- Average insulation thickness: 0.9 mm
- Insulation thickness of neutral conductor: - mm
- Average sheath thickness: 1.3 mm
- Nominal outer diameter: 11.6 mm
- Nominal overall diameter of each phase cable: - mm
- Nominal overall diameter: - mm
- Approximate weight: 140 kg/km
- Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
- Permissible short circuit current conductor 1s: 2.3 kA
ARE4E 0,6/1kV 1x50 IT
Nexans ref. 10548240
- With smaller neutral conductor: No
- Neutral Type:
- Lay Up: Single core
- Number of cores: 1
- Number of phases: -
- Conductor cross-section: 50 mm²
- Phase Conductor Cross Section: - mm²
- Neutral conductor section (when smaller): - mm²
- Conductor diameter: 8.2 mm
- Phase Conductor Diameter: - mm
- Neutral Conductor Diameter: - mm
- Average insulation thickness: 1.0 mm
- Insulation thickness of neutral conductor: - mm
- Average sheath thickness: 1.3 mm
- Nominal outer diameter: 14.1 mm
- Nominal overall diameter of each phase cable: - mm
- Nominal overall diameter: - mm
- Approximate weight: 220 kg/km
- Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
- Permissible short circuit current conductor 1s: 4.7 kA
ARE4E 0,6/1kV 1x95 IT
Nexans ref. 10548242
- With smaller neutral conductor: No
- Neutral Type:
- Lay Up: Single core
- Number of cores: 1
- Number of phases: -
- Conductor cross-section: 95 mm²
- Phase Conductor Cross Section: - mm²
- Neutral conductor section (when smaller): - mm²
- Conductor diameter: 11.5 mm
- Phase Conductor Diameter: - mm
- Neutral Conductor Diameter: - mm
- Average insulation thickness: 1.1 mm
- Insulation thickness of neutral conductor: - mm
- Average sheath thickness: 1.4 mm
- Nominal outer diameter: 18.0 mm
- Nominal overall diameter of each phase cable: - mm
- Nominal overall diameter: - mm
- Approximate weight: 380 kg/km
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- Permissible short circuit current conductor 1s: 8.9 kA
ARE4EX 0,6/1kV 3x150+95N IT
Nexans ref. 10548249
- With smaller neutral conductor: Yes
- Neutral Type: Aluminium - Class 2 acc. to IEC 60228
- Lay Up: Twisted single cores
- Number of cores: 4
- Number of phases: 3
- Conductor cross-section: - mm²
- Phase Conductor Cross Section: 150 mm²
- Neutral conductor section (when smaller): 95 mm²
- Conductor diameter: - mm
- Phase Conductor Diameter: 14.3 mm
- Neutral Conductor Diameter: 11.5 mm
- Average insulation thickness: 1.4 mm
- Insulation thickness of neutral conductor: 1.10 mm
- Average sheath thickness: 1.4 mm
- Nominal outer diameter: - mm
- Nominal overall diameter of each phase cable: 21.6 mm
- Nominal overall diameter: 50.0 mm
- Approximate weight: 2040 kg/km
- Max. DC resistance of the conductor at 20°C: - Ohm/km
- Permissible short circuit current conductor 1s: - kA
ARE4EX 0,6/1kV 3x240+150N IT
Nexans ref. 10547934
- With smaller neutral conductor: Yes
- Neutral Type: Aluminium - Class 2 acc. to IEC 60228
- Lay Up: Twisted single cores
- Number of cores: 4
- Number of phases: 3
- Conductor cross-section: - mm²
- Phase Conductor Cross Section: 240 mm²
- Neutral conductor section (when smaller): 150 mm²
- Conductor diameter: - mm
- Phase Conductor Diameter: 18.5 mm
- Neutral Conductor Diameter: 14.3 mm
- Average insulation thickness: 1.7 mm
- Insulation thickness of neutral conductor: 1.40 mm
- Average sheath thickness: 1.5 mm
- Nominal outer diameter: - mm
- Nominal overall diameter of each phase cable: 26.9 mm
- Nominal overall diameter: 61.7 mm
- Approximate weight: 3200 kg/km
- Max. DC resistance of the conductor at 20°C: - Ohm/km
- Permissible short circuit current conductor 1s: - kA
Description
Description
Standards
-
NationalGSC002
Description
Single core and helically bundled tetra polar cables with aluminium conductor, XLPE insulation, polyolefin outer sheath.
Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.
Fire performance class: Eca
Application:
Suitable for fixed installation laying indirectly buried.
Construction
- Conductor: stranded, compacted, round aluminium – Cl. 2 (CEI EN 60228).
- Insulation: extruded polyethylene (XLPE) compound.
- Outer sheath: extruded polyolefin (PO) compound. Colour: black.
Functional characteristics
- Rated voltages U0/U: 0,6/1 kV
- Max. operating temperature of conductor: 90°C
- Max. short circuit temperature of conductor: 250°C (max 5s)
- Min. installation temperature: -25°C
- Max. tensile strength on the conductor during installation: 50 N/mm2
- Min. bending radius during installation (single core cables): 6 Dcable
- Min. bending radius during installation (quadripolar cables): 9 Dphase
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Insulation
Extruded XLPE compound
Insulation colour
Natural
Outer sheath
Extruded polyolefin-based thermoplastic compound
Sheath colour
Black
Dimensional characteristics
Dimensional characteristics
Sheath thickness of the neutral conductor
1.40 mm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV