ARE4E 0,6/1kV 1x95 IT
Description
Description
Standards
-
NationalGSC002
Single core and helically bundled tetra polar cables with aluminium conductor, XLPE insulation, polyolefin outer sheath.
Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.
Fire performance class: Eca
Application:
Suitable for fixed installation laying indirectly buried.
Construction:
- Conductor: stranded, compacted, round aluminium – Cl. 2 (CEI EN 60228).
- Insulation: extruded polyethylene (XLPE) compound.
- Outer sheath: extruded polyolefin (PO) compound. Colour: black.
Functional characteristics:
- Rated voltages U0/U: 0,6/1 kV
- Max. operating temperature of conductor: 90°C
- Max. short circuit temperature of conductor: 250°C (max 5s)
- Min. installation temperature: -25°C
- Max. tensile strength on the conductor during installation: 50 N/mm2
- Min. bending radius during installation (single core cables): 6 Dcable
- Min. bending radius during installation (quadripolar cables): 9 Dphase
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
With smaller neutral conductor
No
Neutral Type
Insulation
Extruded XLPE compound
Insulation colour
Natural
Lay Up
Single core
Outer sheath
Extruded polyolefin-based thermoplastic compound
Sheath colour
Black
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Number of phases
-
Conductor cross-section
95 mm²
Phase Conductor Cross Section
- mm²
Neutral conductor section (when smaller)
- mm²
Conductor diameter
11.5 mm
Phase Conductor Diameter
- mm
Neutral Conductor Diameter
- mm
Average insulation thickness
1.1 mm
Insulation thickness of neutral conductor
- mm
Average sheath thickness
1.4 mm
Sheath thickness of the neutral conductor
- mm
Nominal outer diameter
18.0 mm
Nominal overall diameter of each phase cable
- mm
Nominal overall diameter
- mm
Approximate weight
380 kg/km
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Permissible short circuit current conductor 1s
8.9 kA
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1000787-ITBP
- Certification Date : 12/10/20
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 0051
- Declared performance : Eca