ARE4H5EXY 12/20kV 3x150+50Y IT

Description

Description

Standards

  • Product
    GSCC008

Helically bundled tripolar cables, with messenger. Phases with aluminium conductor, XLPE insulation, aluminium tape screen, PE outer sheath. Messenger with aluminium clad steel conductor.

Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.

Fire performance class:  Fca

Application:

Suitable for fixed installation laying in air.

Construction:

  • Conductor: stranded, compacted, round aluminium – Cl. 2 (IEC 60228).
  • Conductor screen: extruded semiconducting compound.
  • Insulation: extruded polyethylene (XLPE) compound.
  • Insulation screen: extruded semiconducting compound – easy strippable.
  • Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,3 mm).
  • Outer sheath: extruded polyethylene (PE) compound. Colour: grey.
  • Messenger: stranded aluminium clad steel wires.

Functional characteristics:

  • Rated voltages U0/U: 12/20 kV
  • Max. operating temperature of conductor: 90°C
  • Max. short circuit temperature of conductor: 250°C (max 5s)
  • Max. short circuit temperature of screen: 150°C
  • Min. installation temperature: -25°C
  • Max. tensile strength on the conductor during installation: 50 N/mm2
  • Min. bending radius during installation: 21 Dphase

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Material of the inner semi-conductor
Extruded semiconducting compound
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded semiconducting compound - easy strippable
Screen
Aluminium tape
Outer sheath
Extruded PE compound
Sheath colour
Grey
Messenger
Aluminium clad steel
Messenger shape
Round, stranded
Messenger flexibility
According to GSCC008
Lay Up
Twisted single cores

Dimensional characteristics

Dimensional characteristics

Number of phases
3
Phase Conductor Cross Section
150 mm²
Messenger cross-section
49.48 mm²
Phase Conductor Diameter
14.3 mm
Messenger conductor diameter
9 mm
Nominal insulation thickness
4.9 mm
Minimum insulation thickness
4.31 mm
Diameter over insulation
24.7 mm
Screen thickness
300 µm
Average sheath thickness
2.0 mm
Nominal overall diameter of each phase cable
32.7 mm
Nominal overall diameter
74.8 mm
Approximate weight
3400 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Max. DC resistance of the conductor at 20°C
0.206 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.265 Ohm/km
Permissible current rating in air 40°C - trefoil formation
340 A
Permissible short circuit current conductor 1s
14.2 kA
Permissible short circuit current screen 0.5s
2.6 kA
Grounding type
Solid bonding

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000773-ITBP
  • Certification Date : 12/10/20
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0051
  • Declared performance : Fca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close